Kunlun automatic tank gauge Note before installation:
You should use oil dip rod to inspect whether the real installation height of the tank is consistent with the length of the probe that we supply.

Open the box to check the accessory list in order to examine whether there is any transport failure.

Kunlun ATG system Installation:

Fetch the flange at the tank’s fuel hatches.

Insert the probe into the installation orifice of the installation flange.

Install the Ajustable fitting,O-ring seal,Flange,Product Float, Interface Float and the Nylon Stopper on the probe in turn, then lock the Snap Ring.

Insert the probe into the fuel hatches.

Raise the probe after it is put at the bottom of the tank, make sure that the distance between the end of the probe and the bottom of the tank is 2~10mm,prevent the probe from getting curving and screw down the probe locknut.

Install the installation flange closely.